Publication 1747-UM655B-EN-P - June 2007

36 Hardware Setup

Dip Switch Setting

For the example application, we used the following configuration to
match the configuration of the SLC 500 processor’s RS-232 port
described in the previous section.

For this configuration, set the switches as shown in these tables.

Channel 0 Configuration

Attribute

Value

DF1 station address

0

Communication rate

19.2 Kbps

Full/Half-duplex

Full-duplex

Parity

None

Handshake

No handshaking

Diagnostic command execution

Disabled

Duplicate detect

Enabled

Error detect

CRC

Retries

3

DF1 ACK timeout

1.0 s

The upper position as shown above is
ON. The lower position is OFF.