Publication 1747-UM655B-EN-P - June 2007

108 AutoScan

9. Return the scanner to Run mode (bit 0 in the scanner control

output word is set to 1) and the scanner status display should be
displaying the scanner node address.

If the status display is flashing other codes as well, refer
Chapter 7 for troubleshooting.

Enabling AutoScan via the DeviceNet Configuration Terminal

Follow these steps to enable the AutoScan feature using the
DeviceNet configuration terminal (DNCT).

1. Verify that the scanner is in Idle mode (bit 0 in the scanner

control output word is 0) and that all slave nodes are connected
and communicating on the DeviceNet network.

2. Plug the DNCT terminal into the DeviceNet network.

3. Select 1747-SDN module from the Network Who screen by

pressing the E/Enter key.

4. Use the D/Down-arrow key to highlight Scanner, then select it

by pressing the E/Enter key.

5. Use the D/Down-arrow key to highlight AutoScan, then select it

by pressing the E/Enter key.