Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual

Page 117

Advertising
background image

Publication 1747-UM655B-EN-P - June 2007

Data Map Example 117

In this example, nothing is mapped to the DeviceNet input
data area of the processor's M1 file. All input data is mapped
to the processor's input image table via the scanner's
discrete-input data table.

DeviceNet Message
from Node #11

1 byte

S

D

1747-SDN Module
Discrete-input Data Table

15

31

47

63

11

0

16

32

48

Word 1

Word 2

Word 3

Word 4

15

0 Word 0

15

31

47

63

11

0

16

32

48

Word 1

Word 2

Word 3

Word 4

Bit Number

Word 0

Status

Words 1…31

DeviceNet Input Data (31 Words)

Words 0…149

DeviceNet Input Data (150 Words)

Words 150…210

Reserved (61 Words)

Word 211

Scan Counter (1 Word)

WordS 212…215

Device Active Table (4 Words)

Words 216…219

Device Failure Table (4 Words)

Words 220…223

Auto Verify Table (4 Words)

Words 224…255

Client Server Table (32 Words)

SLC Processor M1 File