146 Explicit Message Program Control
For each upload, the status code provides the processor with status on
the device and its response.
Command Code
Description
0
Ignore transaction block (block empty)
1
Execute this transaction block
2
Get status of transaction TXID
3
Reset all client/server transactions
4
Delete transaction from response queue
5…255
Reserved
Status Code
Description
0
Ignore transaction block (block empty)
1
Transaction completed successfully
2
Transaction in progress (not ready)
3
Error – slave not in scanlist
4
Error – slave offline
5
Error – DeviceNet port disabled/offline
6
Error – transaction TXID unknown
7
Error – slave not responding to explicit
request
8
Error – invalid command code
9
Error – scanner out of buffers
10
Error – other Client/server transaction in
progress
11
Error – could not connect to slave device
12
Error – response data too large for block
13
Error – invalid port
14
Error – invalid size specified
15
Error – connection busy
16…255
Reserved