Download and run the program via a dh+ network – Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual

Page 86

Advertising
background image

Publication 1747-UM655B-EN-P - June 2007

86 Creating and Running the Example Application Program

Download and Run the Program via a DH+ Network

Follow the procedure below to download and run the example
program via a DH+ network.

1. From the RSLogix 500 Communication menu, choose System

Communication.

RSLinx software starts, and the Communication dialog opens.

2. Select your Data Highway Plus driver (AB_KT-1, Data Highway

Plus in the above example).

3. Select the + next to your Data Highway Plus driver (AB_KT-1

above) to expand the tree.

4. Select the SLC 500 processor and click Download.

5. Go Online and put the SLC 500 processor in Run mode after the

download is complete.

IMPORTANT

You must also place the 1747-SDN module in Run mode by
setting the Run bit (bit 0) in the scanner’s command register.
The command register is located at word 0 in the Output image
table.

Advertising