Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual

Page 119

Advertising
background image

Publication 1747-UM655B-EN-P - June 2007

Data Map Example 119

The processor writes output data for each scanned device in the
scanner's discrete-output data table. The scanner then maps each bit
into a strobe message that is sent to all scanned devices. The bit
number, where a particular device's data is mapped, directly
corresponds to that device's MAC ID. This is true for mapping into the
scanner's data table as well as the scanner's strobe message. For
example, node # 11's output bit is mapped in bit number 11 of the
scanner's output data table. In addition, this same output bit is
mapped from bit 11 of the data table to bit number 11 in the strobe
message.

In this example, nothing is mapped from the DeviceNet output
data area of the processor's M0 file. All output data is mapped
from the processor's output image table to the scanner's
discrete-input data table.

1747-SDN Output Strobe Message

The strobe message contains one bit for
each scanned device on the network.

1747-SDN Module Discrete
Output Data Table

15

31

47

63

11

0

16

32

48

Word 1

Word 2

Word 3

Word 4

15

0 Word 0

Word 0

Command (1 Word)

Words 1…31

Device Output Data (31 Words)

Words 0…223

DeviceNet Output Data (224 Words)

Words 224…255

Client Server Table (32 Words)

SLC Processor M0 File

SLC Processor Output Image Table

Bit Number

63 - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - 0

11