Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual
Page 77
![background image](/manuals/579400/77/background.png)
Publication 1747-UM655B-EN-P - June 2007
Communicating with the DeviceNet Network from Another Network 77
The Browse for network dialog appears. You see the drivers you
have configured on your system.
5. Select the 1747-SDNPT-3 driver and click OK.
You receive the following prompt.
6. Click OK to upload the devices.
RSNetWorx for DeviceNet software begins browsing for network
devices.
The network should look similar to the one shown below when
the software is finished browsing.
ATTENTION
Performing a pass-through browse via the DH+ network takes
longer than browsing by using the 1770-KFD DeviceNet driver
as described in chapter 4.
Note that due to the time required, the pass-through method is
not suitable for configuring a network nor for real time
monitoring of your network devices.
TIP
If RSNetWorx for DeviceNet software fails to find a device,
check the physical connection to that device.