Block Transfer Write and Block Transfer Read Configurations for 2 Output/6 Input 1771-N Series Modules

E–4

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Bit 15 (17)

CJ alarm enable. A value of 1 enables over and underrange

indication for the cold junction channel. If the module does not

have a cold junction channel, this bit is 0.

Word 4

Bits 00-15

(00-17)

Real time sample. Sample time in milliseconds. 0 = off.

RTS minimum is 100msec (counts = 100). Maximum 10

seconds in binary; 9.999 seconds in BCD.

Word 5

Bits 00-15

(00-17)

Low scale value for channel 1. Scale values are limited to

+32767 in binary format; +7999 in BCD format.

Word 6

Bits 00-15

(00-17)

High scale value for channel 1. Scale values are limited to

+32767 in binary format; +7999 in BCD format.

Word 7

Bits 00-15

(00-17)

Low clamp value for channel 1. The channel output will not be

allowed to go below this value (in scaled units) regardless of

the data sent to the module. Clamp values are limited to

+32767 in binary format; +7999 in BCD format.

Word 8

Bits 00-15

(00-17)

High clamp value for channel 1. The channel output will not be

allowed to go above this value (in scaled units) regardless of

the data sent to the module. Clamp values are limited to

+32767 in binary format; +7999 in BCD format.

Bits 00-11

(00-13)

Maximum ramp rate. If this field is not 0, the module will limit

the maximum rate of change for this channel to be a

percentage of the scaled range of the module. Legal values

are from 1 to 200%.

Bit 12 (14)

Constant = 0

Word 9

Bits 13-14

(15-16)

Reset state. This field controls what the channel will output if

the I/O reset line is asserted:

00 binary = last state;

01 binary = minimum output; (example: < -10V, < 4mA)

10 binary = maximum output; (example: > 10V, > 22mA)

11 binary = user reset value.

Bit 15 (17)

Alarm enable. If set to 1, the module reports high clamp, low

clamp and rate limit. If 0, these warnings are suppressed.

Word 10

Bits 00-15

(00-17)

Reset value. If the user selects the channel to go to a user

reset value upon I/O reset, the value in scaled units is entered

here. Otherwise, set to 0.

Word 11 thru 16

Same as words 5 thru 10 but for channel 2.

Word 17

Bits 00-15

(00-17)

Low scale value for channel 3.

Word 18

Bits 00-15

(00-17)

High scale value for channel 3.

Word 19

Bits 00-15

(00-17)

Low alarm value for channel 3.

Word 20

Bits 00-15

(00-17)

High alarm value for channel 3.

Word 21

Bits 00-14

(00-16)

Rate alarm. If the channel's input changes at a rate faster than

this value and the alarm enable bit is set, the channel will

indicate a rate alarm condition. Legal values are from 0.05 to

50% of full scale per second.