Configuring the Module

Publication 1771ĆUM127B-EN-P - December 2002

Bit/Word Description of Output Configuration Words 3 and 4

Word

Decimal Bit

(Octal Bit)

Definition

Word 3

Bit 00

Verify. If this bit is set to 1, the module will compare its current

programming with the programming downloaded in the BTW. If

they are the same, it will verify good; if they are different, the

module will verify bad. In no case will any programming data in

the BTW be applied to the module.

Bit 01

Temperature scale. 0 = Celsius, 1 = Fahrenheit

Bit 02

BCD select.

1 = all values in BCD format.

0 = all values in 2's complement binary

Bits 03Ć14

(03Ć16)

Not used. Always 0

Bit 15 (17)

CJ alarm enable. A value of 1 enables over and underrange

indication for the cold junction channel. If the module does not

have a cold junction channel, this bit is 0.

Word 4

Bits 00Ć15

(00Ć17)

Real time sample. Sample time in milliseconds. 0 = off.

RTS minimum is 100msec (counts = 100). Maximum 10

seconds in binary; 9.999 seconds in BCD.

Output Programming
The next group of six words contain channel-specific parameters.
This includes low and high scale values, low and high clamp values,
ramp rate, reset state, alarm enable and reset value.

Output Configuration Words 5 through 10

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Channel 1 Programming

5

Low Scale Value

6

High Scale Value

7

Low Clamp Value

8

High Clamp Value

9

Alarm

enable

Reset State

0

Maximum Ramp Rate, % of Full Scale per second

10

Reset Value