Block Transfer Write and Block Transfer Read Configurations for 0 Output/8 Input 1771-N Series Modules

B–8

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Bit 04

Low alarm. This bit is set if alarms are enabled and the input

data is lower than the low alarm setpoint.

Bit 05

High alarm. This bit is set if alarms are enabled and the input

data is higher than the high alarm setpoint.

Bit 06

Rate alarm. This bit is set if the input signal changed at a rate

faster than the input rate alarm setpoint.

Word 4 continued

Bit 07

Not used. Always 0

Bit 08 (10)

Bad program. This bit is set if any of the channel level

programming data is illegal.

Bit 09 (11)

Bad calibration. This bit is set if the channel has not had a valid

calibration.

Bits 10-14

(12-16)

Not used. Always 0

Bit 15 (17)

Not used. Always = 1

Word 5

Bits 00-15

(00-17)

Channel 1 input data.

Words 6 and 7

Same as words 4 and 5 but for Channel 2

Words 8 and 9

Same as words 4 and 5 but for Channel 3

Words 10 and 11

Same as words 4 and 5 but for Channel 4

Words 12 and 13

Same as words 4 and 5 but for Channel 5

Words 14 and 15

Same as words 4 and 5 but for Channel 6

Words 16 and 17

Same as words 4 and 5 but for Channel 7

Words 18 and 19

Same as words 4 and 5 but for Channel 8

Words 20 thru 27

For factory use only