Appendix, What this appendix contains – Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 123

Appendix
F
Publication 1771ĆUM127B-EN-P - December 2002
Block Transfer Write and Block
Transfer Read Configurations
for 1 Output/7 Input 1771ĆN
Series Modules
This appendix contains block transfer write and block transfer read
configurations and bit/word descriptions for 1771-N series modules
with one output and seven inputs.
Block Transfer Write Configuration Block for 1 Output/7 Input
Modules
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
BTW word type
Constant
Number of outputs
Constant
0
1
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
1
Channel 1 Output Data
2
CJ alarm
enable
Unused = 0
BCD
select
Temp
scale
Verify
3
RTS Sample Time: 1 millisecond units
Channel 1 Programming
4
Low Scale Value
5
High Scale Value
6
Low Clamp Value
7
High Clamp Value
8
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
9
Reset Value
Channel 2 Programming
10
Low Scale Value
11
High Scale Value
12
Low Alarm Value
13
High Alarm Value
14
Alarm
enable
Rate Alarm: Scaled Units per second
15
Filter Time Constant: 0.1 second units
Alarm Deadband
16
Thermocouple Type
0
RTD Type
10 Ohm Offset: 0.01 Ohm units
Channel 3 Programming
17
Low Scale Value
18
High Scale Value
What This Appendix
Contains