Block Transfer Write and Block Transfer Read Configurations for 4 Output/4 Input 1771-N Series Modules

H–4

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Bit 00

Verify. If this bit is set to 1, the module will compare its current programming with the

programming downloaded in the BTW. If they are the same, it will verify good; if they

are different, the module will verify bad. In no case will any programming data in the

BTW be applied to the module.

Bit 01

Temperature scale. 0 = Celsius, 1 = Fahrenheit

Word 5

Bit 02

BCD select.

1 = all values in BCD format.

0 = all values in 2's complement binary

Bits 03-14

(03-16)

Not used. Always 0

Bit 15 (17)

CJ alarm enable. A value of 1 enables over and underrange indication for the cold

junction channel. If the module does not have a cold junction channel, this bit is 0.

Word 6

Bits 00-15

(00-17)

Real time sample. Sample time in milliseconds. 0 = off.

RTS minimum is 100msec (counts = 100). Maximum 10 seconds in binary; 9.999

seconds in BCD.

Word 7

Bits 00-15

(00-17)

Low scale value for channel 1. Scale values are limited to +32767 in binary format;

+7999 in BCD format.

Word 8

Bits 00-15

(00-17)

High scale value for channel 1. Scale values are limited to +32767 in binary format;

+7999 in BCD format.

Word 9

Bits 00-15

(00-17)

Low clamp value for channel 1. The channel output will not be allowed to go below

this value (in scaled units) regardless of the data sent to the module. Clamp values

are limited to +32767 in binary format; +7999 in BCD format.

Word 10

Bits 00-15

(00-17)

High clamp value for channel 1. The channel output will not be allowed to go above

this value (in scaled units) regardless of the data sent to the module. Clamp values

are limited to +32767 in binary format; +7999 in BCD format.

Bits 00-11

(00-13)

Maximum ramp rate. If this field is not 0, the module will limit the maximum rate of

change for this channel to be a percentage of the scaled range of the module. Legal

values are from 1 to 200% of full scale/second.

Bit 12 (14)

Constant = 0

Word 11

Bits 13-14

(15-16)

Reset state. This field controls what the channel will output if the I/O reset line is

asserted:

00 binary = last state;

01 binary = minimum output; (example: < -10V, < 4mA)

10 binary = maximum output; (example: > 10V, > 22mA)

11 binary = user reset value.

Bit 15 (17)

Alarm enable. If set to 1, the module reports high clamp, low clamp and rate limit. If

0, these warnings are suppressed.

Word 12

Bits 00-15

(00-17)

Reset value. If the user selects the channel to go to a user reset value upon I/O

reset, the value in scaled units is entered here. Otherwise, set to 0.

Word 13 thru 18

Same as words 7 thru 12 but for channel 2.

Word 19 thru 24

Same as words 7 thru 12 but for channel 3.

Word 25 thru 30

Same as words 7 thru 12 but for channel 4.

Word 31

Bits 00-15

(00-17)

Low scale value for channel 5.

Word 32

Bits 00-15

(00-17)

High scale value for channel 5.

Word 33

Bits 00-15

(00-17)

Low alarm value for channel 5.

Word 34

Bits 00-15

(00-17)

High alarm value for channel 5.