5–7

Module Status and Input Data

Publication 1771ĆUM127B-EN-P - December 2002

Bit/Word Description for Output Status Data Words

Word

Decimal Bit

(Octal Bit)

Definition

Bit 00-03

Not used. Always 0

Bit 04

Low clamp. This bit is set if alarms are enabled and the output

data is lower than the low clamp value.

Bit 05

High clamp. This bit is set if alarms are enabled and the output

data is higher than the high clamp value.

Bit 06

Rate alarm. This bit is set if alarms are enabled and the output

data changed faster than the programmed ramp rate.

Word 4

Bit 07

Bad data. This bit is set if BCD format was chosen and the

output data is not a legal BCD value.

Bits 08 (10)

Bad programming. This bit is set if the most recent BTW

contained improper programming data for this channel

Bit 09 (11)

Bad calibration. This bit is set if the channel has not had a

valid calibration.

Bits 10Ć15

(12Ć17)

Not used. Always = 0

Word 5

Bits 00Ć15

(00Ć17)

Channel 1 Raw data sent to DAC.

Refer to the Appendix specific to your module for block transfer
read configurations.

In this chapter you learned the meaning of the status information that
the modules send to the processor.

Chapter Summary