Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 136

Advertising
background image

Block Transfer Write and Block Transfer Read Configurations for 3 Output/5 Input 1771-N Series Modules

G–4

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Word 5

Bits 00-15

(00-17)

Real time sample. Sample time in milliseconds. 0 = off.

RTS minimum is 100msec (counts = 100). Maximum 10 seconds in binary; 9.999

seconds in BCD.

Word 6

Bits 00-15

(00-17)

Low scale value for channel 1. Scale values are limited to +32767 in binary format;

+7999 in BCD format.

Word 7

Bits 00-15

(00-17)

High scale value for channel 1. Scale values are limited to +32767 in binary format;

+7999 in BCD format.

Word 8

Bits 00-15

(00-17)

Low clamp value for channel 1. The channel output will not be allowed to go below

this value (in scaled units) regardless of the data sent to the module. Clamp values

are limited to +32767 in binary format; +7999 in BCD format.

Word 9

Bits 00-15

(00-17)

High clamp value for channel 1. The channel output will not be allowed to go above

this value (in scaled units) regardless of the data sent to the module. Clamp values

are limited to +32767 in binary format; +7999 in BCD format.

Word 10

Bits 00-11

(00-13)

Maximum ramp rate. If this field is not 0, the module will limit the maximum rate of

change for this channel to be a percentage of the scaled range of the module. Legal

values are from 1 to 200% of full scale/second.

Bit 12 (14)

Constant = 0

Bits 13-14

(15-16)

Reset state. This field controls what the channel will output if the I/O reset line is

asserted:

00 binary = last state;

01 binary = minimum output; (example: < -10V, < 4mA)

10 binary = maximum output; (example: > 10V, > 22mA)

11 binary = user reset value.

Bit 15 (17)

Alarm enable. If set to 1, the module reports high clamp, low clamp and rate limit. If

0, these warnings are suppressed.

Word 11

Bits 00-15

(00-17)

Reset value. If the user selects the channel to go to a user reset value upon I/O

reset, the value in scaled units is entered here. Otherwise, set to 0.

Word 12 thru 17

Same as words 6 thru 11 but for channel 2.

Word 18 thru 23

Same as words 6 thru 11 but for channel 3.

Word 24

Bits 00-15

(00-17)

Low scale value for channel 4.

Word 25

Bits 00-15

(00-17)

High scale value for channel 4.

Word 26

Bits 00-15

(00-17)

Low alarm value for channel 4.

Word 27

Bits 00-15

(00-17)

High alarm value for channel 4.

Word 28

Bits 00-14

(00-16)

Rate alarm. If the channel's input changes at a rate faster than this value and the

alarm enable bit is set, the channel will indicate a rate alarm condition. Legal values

are from 0.05 to 50% of full scale per second.

Bit 15 (17)

Alarm enable bit. If set to 1, the module will report high alarm, low alarm,

underrange, overrange, and rate alarm conditions. If 0, these warnings are

suppressed.

Word 29

Bits 00-07

Alarm deadband. This field creates a hysteresis effect on the low and high alarms.

For an alarm condition to be removed, the input signal must go above the low alarm

limit or below the high alarm limit by an amount equal to the specified deadband.

Alarm deadband values must be less than or equal to one half the difference of the

high and low alarm values.

Advertising