Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 63

Advertising
background image

5–3

Module Status and Input Data

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Word 1 continued

Bit 13 (15)

Module alarm. This bit is set if there is an alarm bit set for one

or more channels. The input alarm bits are low, high alarm and

rate alarm. The output channel alarm bits are low and high

clamp, and the rate limit alarm.

Bit 14 (16)

Bad channel data. This bit is set if the module is in BCD mode

and one or more of the input data values sent in the last BTW

are not legal BCD values.

Bit 15 (17)

Powerup bit. This bit is set until a BTW with programming data

is received by the module.

Word 2

Always 8000 hexadecimal.

Word 3

Not used. Always 0

Inputs Only" and Output/Input" Block Transfer Read

Data Header

This following three-word header is used if the module only has
input channels, or if it contains

both input and output channels.

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

0

Constant = 8800 Hexadecimal

1

Power

up

Bad

Chan.

Data

Mod

Alarm

RTS

Time

out

I/O

Reset

Program

Verify

Mod

Fault

Bad

Prog

Bad

Struct Unused = 0

2

1

Unused = 0

CJC

Over

Range

CJC

Under

Range

3

Cold Junction Temperature; Units of 0.01 degrees C or 0.1 degrees F

The bit/word descriptions for the “inputs only” and “output/input”
header block are shown below.

Word

Decimal Bit

(Octal Bit)

Definition

Word 0

Bits 00Ć15

(00Ć17)

Always = 8800 hexadecimal

Bits 00Ć05

Not used

Word 1

Bit 06

Bad structure. This bit is set if there is an error in the BTW

header.

Bit 07

Bad program. This bit is set if any of the module level

programming data is illegal.