background image

4–16

Configuring the Module

Publication 1771ĆUM127B-EN-P - December 2002

Bit/Word Description of Word 0

Word

Bit

Definition

Word 0

00Ć03

Constant = 0

Bits 04Ć07

Number of outputs = 0010

Bits 10Ć15

Constant = 00 1000

Bits 16Ć17

Block transfer write type = 10

The next group of words sets the outputs of the module, if the
module has outputs. For example, if this is a 2 output/6 input
module, words 1 and 2 would contain the data for the two output
channels. If the module has four outputs, words 1 thru 4 would
contain output channel data.

Output Configuration Words 1 and 2

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

Channel 1 Output Data

2

Channel 2 Output Data

Bit/Word Description of Output Configuration Words 1 and 2

Word

Decimal Bit

(Octal Bit)

Definition

Word 1

Bits 00Ć15 (00Ć17)

First Output channel data

Word 2

Bits 00Ć15 (00Ć17)

Second Output channel data

Additional module configuration data is contained in the next two
words. This includes verify, temperature scale, BCD select, cold
junction alarm enable and real time sample time. These are explained
in the bit/word description.

Output Configuration Words 3 and 4

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

3

CJ alarm

enable

Unused = 0

BCD

select

Temp

scale

Verify

4

RTS Sample Time: 1 millisecond units

Advertising