Specifications

A–2

Publication 1771ĆUM127B-EN-P - December 2002

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g@ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100% AM at 900MHz

EFT/B Immunity

IEC 61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type

None (open style

ConnectingCable(s)

1771ĆNC6 = 1.8m (6ft)

1771ĆNC15 = 4.6m (15ft)

Field WiringArm Wiring

Size

Insulation

Category

14-22AWG (2.5-0.25mm

2

) solid or stranded copper wire rated at

60

o

C or greater

3/64 inch (1.2mm) maximum

2

1

Keying

Between 26 and 28

Between 32 and 34

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61000-6-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial Requirements

C-Tick

2

Australian Radiocommunications Act,compliant

with AS/NZS 2064, Industrial Emissions

1 Use this conductor category information for planningconductor routing. Refer to publication 1770Ć4.1, Industrial Automation Wiringand

GroundingGuidelines."

2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.