RTD Type

This field lets you select the type of sensor connected to a 650 ohm
input channel. This field must be 0 for all other channel types.

Sensor Type

BinaryValue

Decimal 10

09

08

Octal 12

11

10

Resistance

0

0

0

100 Ohm Pt. European Std.

0

0

1

100 Ohm Pt. U.S. Std.

0

1

0

10 Ohm Copper

0

1

1

120 Ohm Nickel

1

0

0

10 Ohm Offset

This field lets you compensate for a small offset error in a 10 ohm
copper RTD. Values can range from -0.99 to +0.99 ohms in units of
0.01 ohms.

For example, if the resistance of a copper RTD used with this
channel was 9.74 ohms at 25

o

C, you would enter -0.26 in this field.

The configuration block for a block transfer write consists of:

module configuration header

output channel data (if applicable)

output channel programming (if applicable)

input channel programming (if applicable)

Block Transfer Write Configuration Data Header

The configuration data header consists of information required for
the processor to properly identify the type of information it will be
receiving.

Module Configuration Data Header

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

0

BTW word type

Constant

Number of outputs

Constant

0

1

0

0

0

1

0

0

0

0

0

1

0

0

0

0

0

Configuration Block for a