Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 74

Advertising
background image

6–6

Module Calibration

Publication 1771ĆUM127B-EN-P - December 2002

Table 6.E

Calibration Block Transfer Read

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

0

Calibration BTR Header = C000H

1

Unused = 0

Range EEPROM

Bad

BTW

2

Input Cal Done bits

3

Output Cal Done bits

4

Input Bad Cal bits

5

Output Bad Cal bits

6

Corrected Channel 1 Data

7

Corrected Channel 2 Data

8

Corrected Channel 3 Data

9

Corrected Channel 4 Data

10

Corrected Channel 5 Data

11

Corrected Channel 6 Data

12

Corrected Channel 7 Data

13

Corrected Channel 8 Data

5. Apply the appropriate high reference signal (Table 6.D) to all

input channels being calibrated (for channel 1, I1 on RTP).

6. Send a block transfer write to the module with word 1 containing

CAL CLK bit (01) = 1, and HI/LO bit (00) = 1.

7. Send a block transfer write to the module with word 1 containing

CAL CLK bit (01) = 0, and HI/LO bit (00) = 1.

8. Request a block transfer read (BTR) from the module. If the

INPUT BAD CAL bit (block transfer read word 4, bit 00, for
channel 1 for example) is reset, and the INPUT CAL DONE bit
(BTR word 2, bit 00 for channel 1 for example) is set, the
procedure is complete.
If the bad BTW bit (word 1, bit 00) is set any time during the
calibration procedure, an error occurred during the calibration
procedure. Repeat the calibration.

If the EEPROM bit (word 1, bit 01) is set, the module has a
hardware fault. The module cannot be calibrated.

If the RANGE bit (word 1, bit 02) is set, the channel(s) did not
calibrate because one of the reference signals was out of range.
Repeat the procedure. If the RANGE bit is set a second time,
either the channel is bad, or there is a problem with the
calibration equipment.

Advertising