Installing the Module
Publication 1771ĆUM127B-EN-P - December 2002
Field wiring to the remote termination panel is the same for all
remote termination panel variations. Refer to Figure 2.4.
Each channel has 4 connections: R, I, O, and S.
•
R = return
•
I = input
•
O = output
•
S = shield
Channel 1 would use R1, I1, O1, and S1; channel 2 would use R2,
I2, O2, and S2; and so on for the remaining channels.
To connect field wiring to the remote termination panel:
1. Strip 3/8 inch (9.25 mm) of insulation from the 22-12 AWG wire.
2. Insert the wire into the open connector slot.
3. Tighten the screw to 4.4–5.2 lb–in. (0.5–0.6Nm) to clamp the
wire.
Figure 2.4
Connecting Wire to the Remote Termination Panel
Remote
Termination
Panel (RTP)
channel 2
19621
Each channel has four connections: R, I, O, and S.
Field wiringto the RTP is the same for all RTP variations.
Channel 1 uses R1, I1, O1, and S1; channel 2 uses R2, I2,
O2, and S2; and so on for the remainingchannels.
I = input
O = output
Field Wiring
S = shield
R = return