Block Transfer Write and Block Transfer Read Configurations for 6 Output/2 Input 1771-N Series Modules

I–6

Publication 1771ĆUM127B-EN-P - December 2002

Definition

Decimal Bit

(Octal Bit)

Word

Bits 00-07

10 ohm offset. Compensates for a resistance offset on a 10

ohm copper RTD. Range of +0.99 ohms, in units of 0.01 ohms.

This field must be 0 for all other RTDs.

Bits 08-10

(10-12)

RTD type. Specifies type of RTD linearization on RTD

channels:

001 = 100 ohm Pt, European standard;

010 = 100 ohm Pt. US standard;

011 = 10 ohm copper;

100 = 120 ohm nickel.

This field is 0 for non-RTD channels.

Word 51

Bit 11 (13)

Constant = 0

Bits 12-15

(14-17)

Thermocouple type. Specifies type of TC linearization on TC

channels.

0000 = millivolts;

0001 = B;

0010 = E;

0011 = J;

0100 = K;

0101 = R;

0110 = S;

0111 = T.

This field must be 0 for non-thermocouple channels.

Words 52 thru 58

Same as words 45 thru 51 but for channel 8.

Block Transfer Read Word Assignments for 6 Output/2 Input

Modules

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

0

Constant = 8800 Hexadecimal

1

Power

up

Bad

Chan.

Data

Mod

Alarm

RTS

Time

out

I/O

Reset

Program

Verify

Mod

Fault

Bad

Prog

Bad

Struct

Unused = 0

2

1

Unused = 0

CJC

Over

Range

CJC

Under

Range

3

Cold Junction Temperature; Units of 0.01 degrees C or 0.1 degrees F

Channel 1 Status

4

0

Unused = 0

Bad

Calib

Bad

Prog

Bad

Data

Rate

Alarm

High

Clamp

Low

Clamp

Unused = 0

5

Channel 1 Raw Count sent to DAC

Channel 2 Status

6

0

Unused = 0

Bad

Calib

Bad

Prog

Bad

Data

Rate

Alarm

High

Clamp

Low

Clamp

Unused = 0

7

Channel 2 Raw Count sent to DAC