Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 174

Block Transfer Write and Block Transfer Read Configurations for 7 Output/1 Input 1771-N Series Modules
K–2
Publication 1771ĆUM127B-EN-P - December 2002
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Word/Dec. Bit
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
Word/Octal Bit
20
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
21
Reset Value
Channel 3 Programming
22
Low Scale Value
23
High Scale Value
24
Low Clamp Value
25
High Clamp Value
26
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
27
Reset Value
Channel 4 Programming
28
Low Scale Value
29
High Scale Value
30
Low Clamp Value
31
High Clamp Value
32
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
33
Reset Value
Channel 5 Programming
34
Low Scale Value
35
High Scale Value
36
Low Clamp Value
37
High Clamp Value
38
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
39
Reset Value
Channel 6 Programming
40
Low Scale Value
41
High Scale Value
42
Low Clamp Value
43
High Clamp Value
44
Alarm
enable
Reset State
0
Maximum Ramp Rate, % of Full Scale per second
45
Reset Value
Channel 7 Programming
46
Low Scale Value
47
High Scale Value
48
Low Clamp Value