Output status data – Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 66

Advertising
background image

5–6

Module Status and Input Data

Publication 1771ĆUM127B-EN-P - December 2002

Output Status Data

Each output channel also has two words associated with it. The first
word contains low and high clamp, rate alarm, bad data, bad program
and bad calibration information for the processor. This is followed
by raw count data for that channel. If the module contains both input
and output channels, the output channel words would immediately
follow the header words.

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Channel 1 Status

4

Unused = 0

Bad

Calib

Bad

Prog

Bad

Data

Rate

Alarm

High

Clamp

Low

Clamp

Unused = 0

5

Channel 1 Raw Count sent to DAC

The above two words would be repeated for each output channel. For
example, if this module had two output channels, the following
words would be used.

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Channel 1 Status

4

Unused = 0

Bad

Calib

Bad

Prog

Bad

Data

Rate

Alarm

High

Clamp

Low

Clamp

Unused = 0

5

Channel 1 Raw Count sent to DAC

Channel 2 Status

6

Unused = 0

Bad

Calib

Bad

Prog

Bad

Data

Rate

Alarm

High

Clamp

Low

Clamp

Unused = 0

7

Channel 2 Raw Count sent to DAC