Output status data – Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 66

5–6
Module Status and Input Data
Publication 1771ĆUM127B-EN-P - December 2002
Output Status Data
Each output channel also has two words associated with it. The first
word contains low and high clamp, rate alarm, bad data, bad program
and bad calibration information for the processor. This is followed
by raw count data for that channel. If the module contains both input
and output channels, the output channel words would immediately
follow the header words.
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Channel 1 Status
4
Unused = 0
Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
5
Channel 1 Raw Count sent to DAC
The above two words would be repeated for each output channel. For
example, if this module had two output channels, the following
words would be used.
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Channel 1 Status
4
Unused = 0
Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
5
Channel 1 Raw Count sent to DAC
Channel 2 Status
6
Unused = 0
Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
7
Channel 2 Raw Count sent to DAC