Block Transfer Write and Block Transfer Read Configurations for 0 Output/8 Input 1771-N Series Modules

B–3

Publication 1771ĆUM127B-EN-P - December 2002

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

Word/Dec. Bit

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Word/Octal Bit

Channel 7 Programming

45

Low Scale Value

46

High Scale Value

47

Low Alarm Value

48

High Alarm Value

49

Alarm

enable

Rate Alarm: Scaled Units per second

50

Filter Time Constant: 0.1 second units

Alarm Deadband

51

Thermocouple Type

0

RTD Type

10 Ohm Offset; 0.01 Ohm units

Channel 8 Programming

52

Low Scale Value

53

High Scale Value

54

Low Alarm Value

55

High Alarm Value

56

Alarm

enable

Rate Alarm: Scaled Units per second

57

Filter Time Constant: 0.1 second units

Alarm Deadband

58

Thermocouple Type

0

RTD Type

10 Ohm Offset; 0.01 Ohm units

Block Transfer Write Bit/Word Descriptions for 8 Input Modules

Word

Decimal Bit

(Octal Bit)

Definition

00-03

Constant = 0

Bits 04-07

Number of outputs = 0000

Word 0

Bits 08-13

(10-15)

Constant = 00 1000 binary

Bits 14-15

(16-17)

Block transfer write type = 10 binary

Word 1

Bit 00

Verify. If this bit is set to 1, the module will compare its current

programming with the programming downloaded in the BTW. If

they are the same, it will verify good; if they are different, the

module will verify bad. In no case will any programming data in

the BTW be applied to the module.

Bit 01

Temperature scale. 0 = Celsius, 1 = Fahrenheit

Bit 02

BCD select.

1 = all values in BCD format.

0 = all values in 2's complement binary