Chapter summary – Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 80

Advertising
background image

7–4

Troubleshooting

Publication 1771ĆUM127B-EN-P - December 2002

Table 7.C

Output Channel Status Word (1 per output channel)

Decimal Bit

(Octal Bit)

Definition

Bit 04

Low clamp. This bit is set if alarms are enabled and the output data is

lower than the low clamp value.

Bit 05

High clamp. This bit is set if alarms are enabled and the output data is

higher than the high clamp value.

Bit 06

Rate alarm. This bit is set if alarms are enabled and the output data

changed faster than the programmed ramp rate.

Bit 07

Bad data. This bit is set if BCD data format was chosen and the output

data was not a legal BCD value.

Bit 08 (10)

Bad program. This bit is set if any of the channel level programming

data is illegal.

Bit 09 (11)

Bad calibration. This bit is set if the channel has not had a valid

calibration.

Table 7.D

Input Channel Status Word (1 per input channel)

Decimal Bit

(Octal Bit)

Definition

Bit 00

Underrange bit. This bit is set if the input signal is below the input

channels minimum range.

Bit 01

Overrange bit. This bit is set if the input signal is above the input

channels maximum range.

Bit 04

Low alarm. This bit is set if alarms are enabled and the input signal is

lower than the low alarm setpoint.

Bit 05

High alarm. This bit is set if alarms are enabled and the input signal is

higher than the high alarm setpoint.

Bit 06

Rate alarm. This bit is set if alarms are enabled and the input signal

changed at a rate faster than the input rate alarm setpoint.

Bit 08 (10)

Bad program. This bit is set if any of the module level programming

data is illegal.

Bit 09 (11)

Bad calibration. This bit is set if the channel has not had a valid

calibration.

In this chapter, you learned how to interpret the status indicators,
status words and troubleshoot your analog module.

Chapter Summary

Advertising