Troubleshooting

We describe how to troubleshoot your module by observing
indicators and by monitoring status bits reported to the processor.

At power-up, the module turns the RUN/FLT indicator to red, then
checks for:

correct RAM operation

EPROM operation

EEPROM operation

After passing initial diagnostics, the module turns the RUN/FLT
indicator to flashing green. The indicator will continue to flash green
until it receives a valid BTW. After the BTW, it will stay solid green
during operation. It will turn red if it detects a fault condition. If the
RUN/FLT indicator is red, block transfers will be inhibited.

The lower CAL/COM indicator flashes green when the module is
communicating with the processor. The speed of the flashing is
dependent upon system speed. If the module is accessed in less than
100ms intervals, the CAL/COM indicator will be solid red.

The module also reports status and specific faults (if they occur) in
every transfer of data to the processor. Monitor the green/red
indicators and status bits in the appropriate word of the BTR file
when troubleshooting your module.

Figure 7.1

Indicators

Indicator

When Green

When Red

RUN/FAULT

flashes - duringinitial powerĆup

solid - first valid block transfer write

successfully completed

solid - a fault is found

CAL/COM

flashes - when communication is taking

place between the PLC processor and

the NĆseries module.

flashes - during

calibration