Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 78

Advertising
background image

7–2

Troubleshooting

Publication 1771ĆUM127B-EN-P - December 2002

Table 7.A shows indications, probable causes and recommended
actions to correct common faults which may occur.

Table 7.A

Troubleshooting Chart

Indication

Probable Cause

Recommended Action

Both indicators are OFF

No power to module

Check power to I/O chassis.

Recycle as necessary.

Both indicators are OFF

Possible short on the module

LED driver failure

Microprocessor, oscillator or EPROM failure

RUN/FLT indicator ON red

If immediately after power-up, indicates RAM or

EPROM failure.

Replace module.

RUN/FLT indicator ON red

If duringoperation, indicates possible

microprocessor or backplane interface failure.

Internal fuse bad

RUN/FLT indicator is

flashinggreen

Power-up diagnostics successfully completed.

Normal operation.

RUN/FLT indicator is solid green

Initial block transfer write successfully completed

CAL/COM indicator is green

(solid or flashing)

Normal operation

None required

CAL/COM indicator is green and

RUN/FLT indicator is green but

module data is wrong(for

example, with cable off, input

channel data values are at

minimum scale values)

Internal module problem

Replace module

Design your program to monitor module and channel status bits, and
to take appropriate action depending on your application
requirements. You may also want to monitor these bits while
troubleshooting with your industrial terminal. The module sets a bit
(1) to indicate it has detected one or more of the following module
conditions as shown in Table 7.B.

The module sets a bit (1) to indicate it has detected one or more of
the following input channel conditions (Table 7.D), or output channel
conditions (Table 7.C).

Troubleshooting with

the Indicators

Status Reported by

the Module

Advertising