4–18

Configuring the Module

Publication 1771ĆUM127B-EN-P - December 2002

Bit/Word Description of Output Configuration Words 5 through 10

Word

Decimal Bit

(Octal Bit)

Definition

Word 5

Bits 00Ć15

(00Ć17)

Low scale value for channel 1. Scale values are limited to

+32767 in binary format; +7999 in BCD format.

Word 6

Bits 00Ć15

(00Ć17)

High scale value for channel 1. Scale values are limited to

+32767 in binary format; +7999 in BCD format.

Word 7

Bits 00Ć15

(00Ć17)

Low clamp value for channel 1. The channel output will not be

allowed to go below this value (in scaled units) regardless of

the data sent to the module. Clamp values are limited to

+32767 in binary format; +7999 in BCD format.

Word 8

Bits 00Ć15

(00Ć17)

High clamp value for channel 1. The channel output will not be

allowed to go above this value (in scaled units) regardless of

the data sent to the module. Clamp values are limited to

+32767 in binary format; +7999 in BCD format.

Word 9

Bits 00Ć11

(00Ć13)

Maximum ramp rate. If this field is not 0, the module will limit

the maximum rate of change for this channel to be a

percentage of the full scale range of the module. Legal values

are from 1 to 200%.

Bit 12 (14)

Constant = 0

Word 9

continued

Bits 13Ć14

(15Ć16)

Reset state. This field controls what an output channel will go

to if the I/O reset line is asserted:

00 binary = last state;

01 binary = minimum output; (example: < Ć10V, < 4mA)

10 binary = maximum output; (example: > 10V, > 22mA)

11 binary = user reset value.

Bit 15 (17)

Alarm enable. If set to 1, the module reports high clamp, low

clamp and rate limit. If 0, these warnings are suppressed.

Word 10

Bits 00Ć15

(00Ć17)

Reset value. If the user selects the channel to go to a user

reset value upon I/O reset, the value in scaled units is entered

here. Otherwise, set to 0.

The above six words of output channel-specific information would
be repeated for the next output channel (2), as shown below. The
bit/word descriptions would be the same as above.

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Channel 2 Programming

11

Low Scale Value

12

High Scale Value

13

Low Clamp Value

14

High Clamp Value

15

Alarm

enable

Reset State

0

Maximum Ramp Rate, % of Full Scale per second

16

Reset Value