Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 48

4–8
Configuring the Module
Publication 1771ĆUM127B-EN-P - December 2002
If both the low scale and high scale values are set to 0, the module
reports data in the default resolution as shown below.
Channel Type
Data Format
Temperature Scale
Resolution
10V Output
Binary
N/A
0.1mV/count
10V Output
BCD
N/A
1mV/count
25mA Output
Binary
N/A
0.1mA
25mA Output
BCD
N/A
1mA
50mA Output
Binary
N/A
0.1mA
50mA Output
BCD
N/A
1mA
5V Input
Binary
N/A
0.1mV
5V Input
BCD
N/A
1mV
10V Input
Binary
N/A
0.1mV
10V Input
BCD
N/A
1mV
4 20mA Input
Binary
N/A
0.1mA
4Ć20mA Input
BCD
N/A
1mA
Binary
Voltage Mode
0.01mV/count
BCD
Voltage Mode
1mV/count
5/+55mV Input
Binary
Celsius Mode
0.1
o
C/count
Ć5/+55mV Input
BCD
Celsius Mode
10
o
C/count
Binary
Fahrenheit Mode
0.1
o
F/count
BCD
Fahrenheit Mode
10
o
F/count
Binary
Voltage Mode
0.01mV/count
BCD
Voltage Mode
1mV/count
100mV Input
Binary
Celsius Mode
0.1
o
C/count
100mV Input
BCD
Celsius Mode
10
o
C/count
Binary
Fahrenheit Mode
0.1
o
F/count
BCD
Fahrenheit Mode
10
o
F/count
Binary
Resistance Mode
0.1 Ohm/count
BCD
Resistance Mode
1 Ohm/count
650 Ohm Input
Binary
Celsius Mode
0.1
o
C/count
650 Ohm Input
BCD
Celsius Mode
10
o
C/count
Binary
Fahrenheit Mode
0.1
o
F/count
BCD
Fahrenheit Mode
10
o
F/count