6–5

Module Calibration

Publication 1771ĆUM127B-EN-P - December 2002

Figure 6.1

Connecting a Resistor or Decade Resistance Box to the Remote

Termination Panel

12935-I

Connect the resistor across terminals

R1-I1 and O1.

640 ohm resistor for

high reference value.

1 ohm resistor for low

reference value.

If usinga decade resistance box,

connect in place of the resistor

Decade resisĆ

tance box

3. Send a block transfer write to the module with word 1 containing

CAL CLK bit (01) = 1, and HI/LO bit (00) = 0.

4. Send a block transfer write to the module with word 1 containing

CAL CLK bit (01) = 0, and HI/LO bit (00) = 0.