Installing the Module

Publication 1771ĆUM127B-EN-P - December 2002

The N-series modules are cable-connected to a remote termination
panel using cat. no. 1771-NC6 (6 ft) or -NC15 (15 ft) cables.

Variations of remote termination panels are used, depending on the
type of module used. These are:

Catalog

Number

Description

1771ĆRTP1 has cold junction compensation for thermocouples
1771ĆRTP3 incorporates resistors and fuses; used primarily for 4Ć20mA inputs

when using+5V inputs (Uses 5mm x 20mm fast acting1/4A fuses

such as Bussmann GMA-1/4, 250V/250mA.)

1771ĆRTP4 a generalĆuse block with straightĆthru wiring that can be used for all

applications except thermocouples

1

1771ĆRT41 a 4Ćchannel block with cold junction compensation for thermocouples
1771ĆRT44 a generalĆuse 4Ćchannel block with straightĆthru wiring that can be

used for all applications except thermocouples

1

1

RTP4 and RT44 can be used with thermocouples if a method of cold junction compensation is provided at

the interface of thermocouple and copper wires within the system.

The remote termination panels are designed for mounting on
standard DIN 1 or DIN 3 mounting rails.

Connecting Wiring