6–4

Module Calibration

Publication 1771ĆUM127B-EN-P - December 2002

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

Word/Dec. Bit

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Word/Octal Bit

9

3rd High Output Cal Value

10

4th Low Output Cal Value

11

4th High Output Cal Value

12

5th Low Output Cal Value

13

5th High Output Cal Value

14

6th Low Output Cal Value

15

6th High Output Cal Value

16

7th Low Output Cal Value

17

7th High Output Cal Value

18

8th Low Output Cal Value

19

8th High Output Cal Value

2. Apply the appropriate low reference signal (Table 6.D) to all

input channels being calibrated (for channel 1, I1 on RTP).

Table 6.D

Calibration Reference Signal Values

Type

Low Reference Value High Reference Value

5 Volt input

0.0000V

5.0000V

10V input

0.0000V

10.0000V

4-20mA sourcinginput

1.000mA

21.000mA

-5 to 55mV/TC input

0.000mV

55.000mV

100mV/TC input

0.000mV

100.000mV

650 Ohm RTD input

1.000 Ohms

649.0 Ohms

10V output

0.000V

10.000V

25mA output

0.500mA

22.000mA

50mA output

1.000mA

50.000mA