Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 100

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

A-38 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

1734-232ASC
1 Channel ASCII Interface Module

Configuration Data

Data Type

Default
Value

Valid Data Values

Serial Character Format
(ASCII Format:
Data Bits / Parity / Stop)

SINT

0

0=7N2
1=7E1
2=7O1
3=8N1
4=8N2
5=8E1
6=8O1
7=7E2
8=7O2

Serial Comm Speed
(Baud Rate of the Serial Port)

SINT

0

0=9600
1=1200
2=2400
3=4800
4=19.2K
5=38.4K

Max Receive Characters

SINT

20

-128 to +127 (0 - 128)

Receive Start Delimiter Mode

SINT

0

0=No Start Delimiter
1=Exclude Start Delimiter
2=Include Start Delimiter

Receive Start Delimiter Character

SINT

58
(0x3A)

Any Valid ASCII Character
(Default is Colon [:])

Receive Record End Mode

SINT

2

0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter

Receive End Delimiter

SINT

13
(0x0d)

Any Valid ASCII Character
(Default is Carr. Return)

Receive String Data Type

SINT

1

0=Array
1=Short String
2=String

Pad Mode

SINT

1

0=Pad Mode Disabled
1=Pad Mode Enabled

Pad Character

SINT

0
(0x00)

Any Valid ASCII Character
(Default is NULL)

Receive Swap Mode

SINT

0

0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled

DeviceNet Handshake Mode

SINT

1

0=Master/Slave
handshake
1=Produce Immediate

Max Transmit Characters

SINT

20

-128 to +127 (0 - 128)