5-2 Diagnostics
Indication
Probable Cause
Module Status
Off
No power applied to device
Alternating Red/Green
LED powerup test (module self-test)
Flashing Red
Recoverable fault has occurred:
• Firmware (NVS) update
• MAC ID changed
• CPU load exceeded
Solid Red
Unrecoverable fault has occurred:
• self test failure (checksum failure at powerup, ramtest
failure at powerup)
• firmware fatal error
Flashing Green
Waiting for connection or ControlNet cable break
Solid Green
Module is operating correctly (normal mode)
Indication
Probable Cause
ControlNet A/B Status
Viewed Together
Both Steady Off
Reset, no power or entire network interface deactivated
Alternating
Red/Green
Self test mode
Alternating Red/Off
Bad/invalid node configuration (such as duplicate MAC ID)
Both Steady Red
Failed link interface
Viewed Individually
Steady Off
Channel disabled or channel not supported
Flashing Red/Green
Invalid link configuration
Flashing Red/Off
Severe Link error - link fault or no MAC frames received
Flashing Green/Off
Temporary channel error or listen-only
Steady Green
Normal operation - MAC frames are being received without
detected errors