5-2 Diagnostics

Indication

Probable Cause

Module Status

Off

No power applied to device

Alternating Red/Green

LED powerup test (module self-test)

Flashing Red

Recoverable fault has occurred:

• Firmware (NVS) update

• MAC ID changed

• CPU load exceeded

Solid Red

Unrecoverable fault has occurred:

• self test failure (checksum failure at powerup, ramtest

failure at powerup)

• firmware fatal error

Flashing Green

Waiting for connection or ControlNet cable break

Solid Green

Module is operating correctly (normal mode)

Indication

Probable Cause

ControlNet A/B Status

Viewed Together

Both Steady Off

Reset, no power or entire network interface deactivated

Alternating
Red/Green

Self test mode

Alternating Red/Off

Bad/invalid node configuration (such as duplicate MAC ID)

Both Steady Red

Failed link interface

Viewed Individually

Steady Off

Channel disabled or channel not supported

Flashing Red/Green

Invalid link configuration

Flashing Red/Off

Severe Link error - link fault or no MAC frames received

Flashing Green/Off

Temporary channel error or listen-only

Steady Green

Normal operation - MAC frames are being received without
detected errors