Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 30

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

3-10 Plan to Use Your Adapter

When using I/O modules with large amounts of data, be aware of the
1734-ACNR adapter data capability. The 1734-ACNR adapter has 586
bytes of memory available for scheduled transmit data. The amount of
data used by an individual connection must also include a small
amount of overhead - 10 bytes per connection. Use the following
formula to track the amount of available scheduled transmit data.

Available Memory =
586 - [(Number of connections * 10) + Sum of all connection sizes]

In the following examples, the system uses a 1734-ACNR adapter with
five 1734-232ASC modules.

In this example, you could add a sixth module if it uses less than 54
bytes of application data with 64 bytes of memory left.
64 = 586 - [(5 * 10) +472]

Application Data Size
(Number of Bytes)

Memory Required

1734-232ASC - 1

100

110

1734-232ASC - 2

88

98

1734-232ASC - 3

96

106

1734-232ASC - 4

96

106

1734-232ASC - 5

92

102

Total Bytes Used

472

522