Publication 1734-UM008B-EN-P - August 2005

A-12 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

1734-IE2V
2 Channel Analog Voltage Input

Configuration Data

Data Type

Default
Value

Valid Data Values

Low Engineering Channel 0

INT

0

-32,768 to 32,767

High Engineering Channel 0

INT

10,000

-32,768 to 32,767

Digital Filter Channel 0

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 0

INT

500

-32,768 to 32,767

High Alarm Limit Channel 0

INT

9,500

-32,768 to 32,767

Low Low Alarm Limit Channel 0

INT

200

-32,768 to 32,767

High High Alarm Limit Channel 0

INT

9,800

-32,768 to 32,767

Range Type Channel 0

SINT

2

0=-10 to +10V
2=0 to 10V

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Low Engineering Channel 1

INT

0

-32,768 to 32,767

High Engineering Channel 1

INT

10,000

-32,768 to 32,767

Digital Filter Channel 1

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 1

INT

500

-32,768 to 32,767

High Alarm Limit Channel 1

INT

9,500

-32,768 to 32,767

Low Low Alarm Limit Channel 1

INT

200

-32,768 to 32,767

High High Alarm Limit Channel 1

INT

9,800

-32,768 to 32,767

Range Type Channel 1

SINT

2

0=-10 to +10V
2=0 to 10V

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Notch Filter (Channel 0 & 1)

SINT

2

1=50Hz
2=60Hz
4=250Hz
6=500Hz

Real Time Sample (Channel 0 & 1)

INT

100

0 to 10,000 ms