1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-35
SSI Word Delay Time Note:
To enter Delay values from +32,768 to +65,535
µs, use this conversion
formula:
Desired Delay Value (in
µs) - 65536 = Entered Delay Value (in
µs).
Example: For a 40ms delay time, 40000 - 65536 = -25536
Sensor Resolution Note:
To enter Resolution values from +32,768 to +65,535
µs, use this
conversion formula:
Desired Resolution Value - 65536 = Entered Resolution Value.
Example: For a 40,000 count sensor, 40000 - 65536 = -25536
Sensor Cycle Note:
To enter Cycle values from +32,768 to +65,535, use this conversion
formula:
Desired Cycle Value - 65536 = Entered Cycle Value.
Example: For 50,000 sensor cycle rotations, 50000 - 65536 =
-15536
1734-SSI
1 Channel Synchronous Serial Interface
Configuration Data
Data Type
Default
Value
Valid Data Values
Compare 1 Control;
Compare1_0
Compare1_1
SINT
BIT 0
BIT 1
0
00=Off
01=Up Direction
10=Down Direction
11=Both Directions