A-34 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-SSI
1 Channel Synchronous Serial Interface
Configuration Data
Data Type
Default
Value
Valid Data Values
Run
SINT
1
0=Module Not Running
1=Module Is Running
Gray Binary
SINT
1
0=Binary Code
1=Gray Code
Word Length
SINT
13
2 to 31
Data Speed
SINT
5
5=125K Baud
6=250K Baud
7=500K Baud
8=1M Baud
9=2M Baud
G2B Convert (Gray to Binary)
SINT
0
0=No Convert
1=Convert
Standardization
(Divide / Shift using Trailing)
SINT
0
0=No Standardization
1=Apply Standardization
SSI Word Delay Time
INT
64
-32,768 to 32,767
µs
(16 - 65,535)
Trailing (No. of Trailing Bits)
SINT
0
0 to 16
Input Latch Control
InputLatch_0
InputLatch_1
SINT
BIT 0
BIT 1
0
00=Off
01=Falling Edge of Input
10=Rising Edge of Input
11=Both Edges of Input
Sensor Resolution
(Positions per Rev. or Stroke)
INT
1
-32,768 to 32,767 counts
(1 - 65,535)
Sensor Cycle
(Total Revolutions or Strokes)
INT
1
-32,768 to 32,767 counts
(1 - 65,535)
Compare 0 Value
DINT
0
-2,147,483,648 to
2,147,483,647
(0 - 4,294,967,295)
Compare 1 Value
DINT
0
-2,147,483,648 to
2,147,483,647
(0 - 4,294,967,295)
Compare 0 Control
Compare0_0
Compare0_1
SINT
BIT 0
BIT 1
0
00=Off
01=Up Direction
10=Down Direction
11=Both Directions