1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-15
1734-IR2
2 Channel RTD Input
Configuration Data
Data Type
Default Value
Valid Data Values
Sensor Type Channel 1
SINT
1
0=Ohms
1=100
Ω Pt α385
2=200
Ω Pt α385
5=100
Ω JPt α3916
6=200
Ω JPt α3916
9=10
Ω Cu α427
10=120
Ω Ni α672
11=100
Ω Ni α618
12=120
Ω Ni α618
Temperature Mode Channel 1
SINT
1
0=Custom Scale
1=°C
2=°F
3=°K
4=°R
Notch Filter (Channel 0 & 1)
SINT
1
0=50Hz
1=60Hz
2=100Hz
3=120Hz
4=200Hz
5=240Hz
6=300Hz
7=400Hz
8=480Hz
Input Data
Data Type
Default Value
Valid Data Values
Data Channel 0
INT
0
-32,768 to 32,767
Data Channel 1
INT
0
-32,768 to 32,767
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Status Byte Channel 1
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Output Data
Data Type
Default Value
Valid Data Values
None