Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 58

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

4-28 Configure the Adapter

• The 1734-ACNR adapter removes all of its ControlNet

connections.

• The 1734-ACNR adapter enters into a state where connections

are not permitted.

• The 1734-ACNR adapter responds to any connection request

with a unique error. General Status 0x0C is the unique error
code that identifies the 1734-ACNR overload mode.

• The1 734-ACNR Adapter Status LED flashes red, indicating a

recoverable fault.

• In this no connections allowed state, the adapter continues to

process messages. This gives you the option of issuing a module
reset to leave the no connections allowed state.

If you encouter this overloaded state, you will not have to
troubleshoot the connections being made and dropped; the
1734-ACNR overload error will be latched.

Alternatively, if you anticipate this event in a fault situation, you can
clear the fault via your program.