Plan to Use Your Adapter 3-7
The ControlNet system places your scheduled transfers in the first part 
of each network update interval. Time is automatically reserved for 
network maintenance. Unscheduled transfers are performed during 
the time remaining in the interval.
Before You Begin
To effectively use your adapter, note the following considerations.
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-ACNR adapter to 
a specific POINT I/O module may not always receive a response from 
the I/O module. In the case where the I/O module does not reply to 
the request, the adapter responds with an error code indicating a 
time-out.
Establish I/O Connections
When you power up a POINT I/O system and establish I/O 
connections, the outputs transition to the Idle state, applying Idle state 
data before going to RUN mode. This occurs even when the controller 
making the connection is already in RUN mode.
IMPORTANT
The ControlNet network reserved time for at least 
one maximum-sized unscheduled transfer per update 
interval. Depending on how much time there is for 
unscheduled messaging, every node may not have a 
chance to send unscheduled data every update 
interval.
. . .
. . .
You reserve a 
specific amount 
of time for all 
scheduled 
operations.
The system 
reserves time for 
network 
maintenance.
Any time remaining is used for 
unscheduled operations.