Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 68

Publication 1734-UM008B-EN-P - August 2005
A-6 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
Discrete 2 POINT Output –
With Over Load and Open
Load Diagnostic Status
1734-OB2E
2 POINT 10V-28V DC Electronically Fused Output, Source
1734-OB2EP
2 POINT 10V-28V DC Electronically Fused Protected Output, Source
Configuration Data
Data Type
Default
Value
Valid Data Values
Fault Mode - POINT 0, 1
SINT, BIT
0
0=Fault Value
1=Hold Last State
Fault Value - POINT 0, 1
SINT, BIT
0
0=Off
1=On
Program Mode - POINT 0, 1
SINT, BIT
0
0=Program Value
1=Hold Last State
Program Value - POINT 0, 1
SINT, BIT
0
0=Off
1=On
No Load Enable - POINT 0, 1
(Wire Off Diagnostic)
SINT, BIT
1
0=Disabled
1=Enabled
Auto Restart Enable - POINT 0, 1
(Over Load Behavior)
SINT, BIT
0
0=Latch Off
1=Auto Retry
Fault Latch Enable - POINT 0, 1
(Open Load or Over Load)
SINT, BIT
0
0=No Latching
1=Alarms Latch
Input Data
Data Type
Default
Value
Valid Data Values
Status Data - POINT 0, 1
(Open Load or Over Load)
SINT, BIT
0
0=Off
1=On (Load Fault)
Output Data
Data Type
Default
Value
Valid Data Values
Output Data - POINT 0, 1
SINT, BIT
0
0=Off
1=On