Configure the Adapter 4-19

7. Click OK.

8. Choose Edits Enabled in the top left of the dialog.

9. From the main menu, choose Network>Properties. The _default

dialog appears.

Specify the following information:

10. Specify a value for Network Update Time - the repetitive time

interval in which data can be sent on the link.

11. Specify a value for Max Scheduled Address - the highest number

node that has scheduled connections to it.

12. Specify a value for Max Unscheduled Address - the node with

the highest MAC ID that can use unscheduled time on the link.

These values are set to 99 by default. Chhange these values to
what is installed in your system. This saves you time because the
controller will not have to search for all of the node addresses.