Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 78

Publication 1734-UM008B-EN-P - August 2005
A-16 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data
Data Type
Default
Value
Valid Data Values
Cold Junction Notch Filter
SINT
1
0=50Hz
1=60Hz
Cold Junction Mode
SINT
1
0=None
1=Channel 0
2=Channel 1
3=Average Both
Low Engineering Channel 0
INT
0
-32,768 to 32,767
High Engineering Channel 0
INT
7,000
-32,768 to 32,767
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Notch Filter Channel 0
SINT
1
0=50Hz
1=60Hz
2=100Hz
3=120Hz
4=200Hz
5=240Hz
6=300Hz
7=400Hz
8=480Hz
Sensor Type Channel 0
SINT
5
0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T
Digital Filter Channel 0
INT
0
0 to 10,000 ms
Low Alarm Limit Channel 0
INT
-32,768
-32,768 to 32,767
High Alarm Limit Channel 0
INT
32,767
-32,768 to 32,767
Low Low Alarm Limit Channel 0
INT
-32,768
-32,768 to 32,767
High High Alarm Limit Channel 0
INT
32,767
-32,768 to 32,767