Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 102

Publication 1734-UM008B-EN-P - August 2005
A-40 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-232ASC
1 Channel ASCII Interface Module
Input Data
Data Type
Default
Value
Valid Data Values
Receive Record Number
SINT
0
-128 to +127 (0 - 255)
Status
TX FIFO Overflow
RX FIFO Overflow
RX Parity Error
Handshake Error
New Data Flag
SINT
BIT 0
BIT 1
BIT 2
BIT 6
BIT 7
0
0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present
Length_Lo
SINT
20
-128 to +127 (0 - 128)
Length_Hi
SINT
0
0 or 1
Data[128]
SINT
0
Received ASCII Message
Output Data
Data Type
Default
Value
Valid Data Values
Transmit Record Number
SINT
0
-128 to +127 (0 - 255)
Receive Record Number
SINT
0
-128 to +127 (0 - 255)
Status
TX FIFO Overflow
RX FIFO Overflow
RX Parity Error
Handshake Error
New Data Flag
SINT
BIT 0
BIT 1
BIT 2
BIT 6
BIT 7
0
0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present
Length_Lo
SINT
20
-128 to +127 (0 - 128)
Length_Hi
SINT
0
0 or 1
Data[128]
SINT
0
Transmitted ASCII Message