Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 102

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

A-40 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

1734-232ASC
1 Channel ASCII Interface Module

Input Data

Data Type

Default
Value

Valid Data Values

Receive Record Number

SINT

0

-128 to +127 (0 - 255)

Status
TX FIFO Overflow

RX FIFO Overflow

RX Parity Error

Handshake Error

New Data Flag

SINT
BIT 0

BIT 1

BIT 2

BIT 6

BIT 7

0

0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present

Length_Lo

SINT

20

-128 to +127 (0 - 128)

Length_Hi

SINT

0

0 or 1

Data[128]

SINT

0

Received ASCII Message

Output Data

Data Type

Default
Value

Valid Data Values

Transmit Record Number

SINT

0

-128 to +127 (0 - 255)

Receive Record Number

SINT

0

-128 to +127 (0 - 255)

Status
TX FIFO Overflow

RX FIFO Overflow

RX Parity Error

Handshake Error

New Data Flag

SINT
BIT 0

BIT 1

BIT 2

BIT 6

BIT 7

0

0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present

Length_Lo

SINT

20

-128 to +127 (0 - 128)

Length_Hi

SINT

0

0 or 1

Data[128]

SINT

0

Transmitted ASCII Message

Advertising