1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-3
Discrete 2 POINT Input
* POINT I/O Modules support the Unsigned Integer data type UINT
(0-65,535 range).
RSLogix5000 supports the signed Integer data type INT (-32,768 to
+32,767 range).
Filter Time Note:
To enter Filter values from +32,768 to +65,535
µs, use this conversion
formula:
Desired Filter Value (in
µs) - 65536 = Entered Filter Value (in
µs).
Example: For a 40ms filter time, 40000 - 65536 = -25536
1734-IA2
2 POINT 120V AC Input
1734-IB2
2 POINT 10V-28V DC Input, Sink
1734-IM2
2 POINT 240V AC Input
1734-IV2
2 POINT 10V-28V DC Input, Source
Configuration Data
Data
Type
Default
Value
Valid Data Values
Filter Off On Time - POINT 0
INT
1,000
-32,768 to 32,767
µs *
(0 - 65,535)
Filter On Off Time - POINT 0
INT
1,000
-32,768 to 32,767
µs *
(0 - 65,535)
Filter Off On Time - POINT 1
INT
1,000
-32,768 to 32,767
µs *
(0 - 65,535)
Filter On Off Time - POINT 1
INT
1,000
-32,768 to 32,767
µs *
(0 - 65,535)
Input Data
Data
Type
Default
Value
Valid Data Values
Input Data - POINT 0, 1
SINT, BIT
0
0=Off
1=On
Output Data
Data
Type
Default
Value
Valid Data Values
None