Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 90

Publication 1734-UM008B-EN-P - August 2005
A-28 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-VHSC24
1 Channel 15-24V DC Very High Speed Counter
1734-VHSC5
1 Channel 5V DC Very High Speed Counter
Output Data
Data Type
Default
Value
Valid Data Values
PWM Value
INT
0
0 to 9500
(0.00% to 95.00%)
Counter Control
Counter Reset
Counter Preset
Value Reset
(Stored / Accumulated Count)
SINT
BIT 0
BIT 1
BIT 2
0
0
0
0
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
Output Control
Output 0 Force
Output 0 Enable
Output 0 Electronic Fuse
Output 0 Diagnostic Speed
Output 1 Force
Output 1 Enable
Output 1 Electronic Fuse
Output 1 Diagnostic Speed
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
0
0
0
0
0
0
0
0
0
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0=< 8ms Response
1=50ms Response
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0=< 8ms Response
1=50ms Response