Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 82
Advertising
Publication 1734-UM008B-EN-P - August 2005
A-20 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Data Type
Default
Value
Valid Data Values
Idle Mode Channel 1
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Input Data
Data Type
Default
Value
Valid Data Values
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Status Byte Channel 1
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Output Data
Data Type
Default
Value
Valid Data Values
Data Channel 0
INT
0
-32,768 to 32,767
Data Channel 1
INT
0
-32,768 to 32,767