Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 101

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-39

Transmit Data / Receive Data / Delimiter / Pad Character Note:

Note that “7 data bits” allows ASCII Character data values of 0 - 127,
which RSLogix5000 does support in the signed Short Integer data type
SINT (-128 to +127 range).

Note that “8 data bits” allows ASCII Character data values of 0 - 255.
To enter values from +128 to +255, use this conversion formula:

Desired Decimal Value - 256 = Entered Decimal Value.
Example: For an ASCII Character value of 128, 128 - 256 = -128

:

1734-232ASC
1 Channel ASCII Interface Module

Configuration Data

Data Type

Default
Value

Valid Data Values

Transmit End Delimiter Mode

SINT

2

0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter

Transmit End Delimiter Character

SINT

13
(0x0d)

Any Valid ASCII Character
(Default is Carr. Return)

Consume String Data Type

SINT

1

0=Array
1=Short String
2=String

Transmit Swap Mode

SINT

0

0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled

DeviceNet Record Header Mode

SINT

0

0=Transmit Handshake
1=Transmit Immediate

Advertising