Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 61

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

Diagnostics 5-3

POINTBus Status

Off

Device not powered - check module status indicator

Alternating
Red/Green

LED powerup test

Flashing Red

Recoverable fault has occurred:

• at power up the number of expected modules does not

equal the number of modules present

• a module is missing

• node fault (I/O connection timeout)

• after power-up of I/O modules is taking place

• collecting identities

• verifying configuration

Red

Unrecoverable fault has occurred:

• Adapter is bus off

• Adapter has failed its duplicate MAC ID check

Flashing Green

Adapter online with no connections established

• adapter chassis size has not been configured

• controller in program/idle mode

• ControlNet cable break

Green

Adapter online with connections established (normal operation, in
run mode)